Skip to main content
Schneider Electric C10B3TM050C — Miniature Circuit Breakers (MCB)

C10B3TM050C ComPacT NSX 50A MCCB, 25kA at 415V

MPNC10B3TM050C
Active

Schneider Electric ComPacT NSX series, C10B3TM050C, 3-pole 50 A thermal-magnetic MCCB, 25 kA Icu at 415 V AC, IP40, toggle control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10B3TM050C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B3TM050C — Ratings
ParameterValue
Rated current (In)50 A at 50 °C
Poles configuration3P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B3TM050C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B3TM050C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10B3TM050C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B3TM050C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B3TM050C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It protects distribution circuits against overload (thermal element) and short-circuit (magnetic element) per EN/IEC 60947-2.

At 440 V that drops to 20 kA; at 500 V to 15 kA. For a 400 V distribution board fed by a 630 kVA transformer (typical fault level around 18–22 kA), this breaker sits comfortably within its envelope.

The TM-D trip unit is thermal-magnetic: the thermal bimetal handles overloads (L protection) with an inverse-time curve; the magnetic coil handles short-circuits (I protection) with a fixed instantaneous threshold. No electronic adjustment, no ground-fault module — this is the fixed-characteristic variant for straightforward distribution where you don't need selective coordination tuning. Rated 50 A at 50 °C; derate per IEC 60947-2 if ambient exceeds that.

Front connections both top and bottom — no rear-access requirement. Width 105 mm, height 161 mm, depth 86 mm.

Frequently asked questions

What is the breaking capacity of C10B3TM050C at 415 V?

25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 440 V it's 20 kA; at 500 V it's 15 kA.

What standards does this MCCB comply with?

EN/IEC 60947-2 for circuit-breaker performance. Also IEC 60664-1 for pollution degree 3 and IEC 60529 for IP40 enclosure protection.

Where can I buy C10B3TM050C and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

MPN
C10B3TM050C