Skip to main content
Schneider Electric C10H3TM032C — Miniature Circuit Breakers (MCB)

Schneider Electric C10H3TM032C ComPacT NSX100H 32A 3P MCCB

MPNC10H3TM032C
Active

Schneider Electric ComPacT NSX100H, C10H3TM032C, 3-pole MCCB, 32 A thermal-magnetic TM-D trip unit, 100 kA Icu at 240 V AC, H breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10H3TM032C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10H3TM032C — Ratings
ParameterValue
Rated current (In)32 A at 50 °C
Poles configuration3P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10H3TM032C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10H3TM032C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10H3TM032C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10H3TM032C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10H3TM032C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C10H3TM032C is a ComPacT NSX100H molded-case circuit breaker from the ComPacT NSX family, a 3-pole unit rated 32 A at 50 °C with a thermal-magnetic TM-D trip unit providing L (overload) and I (short-circuit) protection. This is the H breaking capacity variant, delivering 100 kA Icu at 220/240 V AC and 70 kA at 380/415 V AC per IEC 60947-2 — high enough for most distribution panels where fault current runs hot.

That's enough for most secondary distribution boards fed from a transformer; you'd only need the higher S or L ratings for main incomers or high-fault locations. The 10 kA at 690 V AC covers 690 V systems where fault currents are typically lower.

Overvoltage category III means it's rated for fixed-installation distribution boards. IP40 front face keeps tools and fingers out; IK07 impact resistance handles accidental bumps during panel work. Suitable for isolation per the standard — you can safely use it as a disconnecting means.

Front connections top and bottom make for straightforward bus-bar or cable landing. Five accessory slots accept auxiliary contacts, shunt trips, or under-voltage releases.

Frequently asked questions

Where can I buy C10H3TM032C and get a price?

This part is sourced and quoted to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is the breaking capacity of C10H3TM032C at 415 V?

70 kA Icu at 380/415 V AC per IEC 60947-2 — the H breaking capacity code. At 240 V it reaches 100 kA.

What standards does C10H3TM032C comply with?

EN/IEC 60947-2 for circuit-breaker performance. Pollution degree 3 per IEC 60664-1, overvoltage category III, IP40 front, IK07 impact. Suitable for isolation per the standard.

MPN