The C10H6TM100 is a Schneider Electric ComPacT NSX100H 4-pole circuit breaker with a thermal-magnetic TM-D trip unit rated at 100 A at 40 °C. Its breaking capacity is the headline spec: 70 kA Icu at 380/415 V AC, 65 kA at 440 V, and 50 kA at 500 V, all per IEC 60947-2. The H suffix in the short name NSX100H tells you it's the high-breaking version of the NSX100 frame, sized for distribution duty where fault levels exceed 36 kA.
The TM-D trip unit gives you L and I protection: thermal overload (L) for long-time overcurrents, and magnetic short-circuit (I) for instantaneous faults. No ground-fault module here — the earth-leakage protection is listed as 'Without', so if you need GFCI, you add a Vigi module downstream.
Front connections top and bottom simplify bus-bar and cable routing. IP40 rated (finger-safe), IK07 impact resistance.
Overvoltage category III, utilization category A (non-selectivity for downstream breakers unless specifically coordinated). Relative humidity 0–95%.