Schneider Electric C10M1TM063
MPNC10M1TM063
Active
Circuit breaker, ComPacT NSX100M AC/DC, 40kA/240VAC, 1 pole, TMD trip unit 63A
$2.44Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC DC |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Product or component type | Circuit breaker |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type ii | Fixed |
| Long-time pick-up adjustment type ir (thermal protection) | Fixed |
| Voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 277 V AC 50/60 Hz 250 V DC |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| Breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 250 V DC conforming to IEC 60947-2 |
| Current | 63 A at 40 °C |
All specifications
| Parameter | Value |
|---|---|
| Breaking capacity code | M 40 kA 240 V AC |
| [Ics] rated service breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 250 V DC conforming to IEC 60947-2 |
| Power dissipation per pole | 8.61 W |
| Network frequency | 50/60 Hz |
| Poles description | 1P |
| Protected poles description | 1D |
| Utilisation category | Category A |
| IK degree of protection | IK07 conforming to IEC 62262 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Circuit breaker mounting mode | Fixed |
| Connection pitch | 35 mm |
| Upside connection | Front |
| Downside connection | Front |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Relative humidity | 0...95 % |
| Operating altitude | 0...2000 m without derating 2000 m...5000 m with derating |
| Electrical shock protection class | Class II on front face |
| Depth | 86 mm |
| Width | 35 mm |
| Height | 161 mm |
| Electrical durability | 20000 cycles at 277 V In/2 10000 cycles at 277 V In |
| Mechanical durability | 20000 cycles |
| Standards | EN/IEC 60947-2 |
| Range | ComPacT |
| Trip unit name | TM-D |
| Trip unit rating | 63 A at 40 °C |
| Device short name | NSX100M |
| Device application | Distribution |
| Overvoltage category | IV |
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Trip unit protection functions | LI |
| Ambient air temperature for storage | -50...85 °C |
| Ambient air temperature for operation | -25...70 °C |
| [Ir] long-time protection pick-up adjustment range | 1 x In |
| [Ii] instantaneous protection pick-up adjustment range | 500 A |
MPN
C10M1TM063