Skip to main content
Schneider Electric C10R3MA013 — Miniature Circuit Breakers (MCB)

Schneider ComPacT NSX C10R3MA013 MCCB, 12.5 A, 200 kA

MPNC10R3MA013
Active

Schneider Electric ComPacT NSX, C10R3MA013, 3-pole MCCB, 12.5 A, MA magnetic trip unit, 200 kA Icu at 415 V AC, motor protection.

$11.58Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10R3MA013 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationMotor protection
C10R3MA013 — Ratings
ParameterValue
Rated current (In)12.5 A at 65 °C
Poles configuration3P
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10R3MA013 — Protection
ParameterValue
Trip unit technologyMagnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C10R3MA013 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10R3MA013 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10R3MA013 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10R3MA013 — Specifications
ParameterValue
Trip unit protection functionsI

Product details

The Schneider Electric C10R3MA013 is a ComPacT NSX100R three-pole moulded-case circuit breaker (MCCB) with a magnetic-only MA trip unit rated 12.5 A at 65 °C, built for motor protection in industrial power distribution. The MA trip unit provides magnetic-only short-circuit protection (I), meaning it responds to fault currents but not to overloads — the motor starter's overload relay handles thermal protection. This coordination keeps the breaker from tripping on motor inrush while still clearing a bolted fault.

Breaking capacity that keeps the line running

Rated 200 kA Icu at 415 V AC (50/60 Hz) per IEC 60947-2, this breaker can interrupt a 200 kA prospective fault current without damage — selectivity headroom for a high-fault point in the distribution, like a motor control centre fed by a large transformer. At 690 V AC the Icu drops to 45 kA; at 525 V AC it holds 65 kA.

Connection pitch 35 mm. IP40 enclosure protection, IK07 impact resistance.

Frequently asked questions

What is the breaking capacity of C10R3MA013?

200 kA Icu at 415 V AC 50/60 Hz per IEC 60947-2, with lower ratings at higher voltages: 80 kA at 500 V, 65 kA at 525 V, 45 kA at 690 V.

What is the MA trip unit for?

The MA trip unit provides magnetic-only short-circuit protection (I), designed for motor protection where the overload relay handles thermal protection and the breaker clears faults only.

MPN
C10R3MA013