Skip to main content
Schneider Electric C10W45E100 — Miniature Circuit Breakers (MCB)

Schneider C10W45E100 ComPacT NSX 100A, 100kA 690V

MPNC10W45E100
Active

Schneider Electric ComPacT NSX, MicroLogic 5.2 E trip unit, 100 A at 40 °C, 100 kA Icu at 690 V AC, 4 poles, backplate mount.

$15.41Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10W45E100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10W45E100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10W45E100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C10W45E100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10W45E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10W45E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10W45E100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSI

Product details

The Schneider Electric C10W45E100 is a ComPacT NSX molded-case circuit breaker with a MicroLogic 5.2 E electronic trip unit, rated 100 A at 40 °C. It carries a 100 kA Icu breaking capacity at 690 V AC 50/60 Hz per IEC 60947-2, which means it can safely interrupt fault currents up to that level without upstream cascading — sized for high-fault-capacity distribution panels where a standard 25 kA or 36 kA breaker would need a current-limiting fuse or a larger upstream device. The 4-pole (4P) configuration with neutral on the left suits three-phase plus neutral distribution in commercial and industrial switchboards. The electronic trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection curves, plus integrated energy metering — demand current/power, power quality indicators, time-stamped event logs, and protection/alarm settings are all communicated via the breaker's data interface.

IK07 impact rating per IEC 62262 means the enclosure withstands a 2 J hammer blow — adequate for general industrial panel environments where accidental tool drops happen. Five accessory slots allow plug-in modules for communication, auxiliary contacts, shunt trips, or under-voltage releases without rewiring the main circuit.

Durability and environmental limits

Rated for 20,000 mechanical cycles and 20,000 electrical cycles at 440 V In/2, 10,000 cycles at 440 V In, and 5,000 cycles at 690 V In/2. That electrical endurance at full rated voltage is typical for a distribution breaker — not designed for frequent switching like a contactor, but adequate for infrequent load isolation and fault interruption.

Frequently asked questions

What is C10W45E100's breaking capacity at 690 V?

The C10W45E100 carries a 100 kA Icu breaking capacity at 660/690 V AC 50/60 Hz per IEC 60947-2. It also delivers 100 kA Icu at 500 V and 525 V AC.

What protection curves does the MicroLogic 5.2 E trip unit provide?

The MicroLogic 5.2 E provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection. It is an electronic trip unit with integrated energy metering.

Where can I buy C10W45E100 and how is it quoted?

The C10W45E100 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance standards does C10W45E100 meet?

The C10W45E100 complies with EN/IEC 60947-2 for low-voltage switchgear and controlgear. It is rated for pollution degree 3 per IEC 60664-1 and overvoltage category III.

MPN