Skip to main content
Schneider Electric C11B4TM025B — Miniature Circuit Breakers (MCB)

Schneider Electric C11B4TM025B ComPacT NSXm Circuit Breaker,

MPNC11B4TM025B
Active

Schneider Electric ComPacT NSXm, circuit breaker, 4P, 25 A at 40 °C, TM-D trip unit, 25 kA at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11B4TM025B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11B4TM025B — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11B4TM025B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11B4TM025B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11B4TM025B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11B4TM025B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11B4TM025B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11B4TM025B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It provides distribution-level overcurrent protection and isolation, certified to EN/IEC 60947-2.

Mounts on a backplate in horizontal or vertical orientation. The 108 mm width occupies 12 module pitches at 9 mm each — standard for DIN-rail panel layouts. Front-facing connections accept compression lugs or busbars; neutral is on the left.

Environmental and electrical ratings

IP40 enclosure protection (IK07 impact) suits clean indoor panels. Electrical durability: 20,000 cycles at 440 V at rated current, 10,000 cycles at 440 V at In, and 5,000 cycles at 690 V at In.

Frequently asked questions

What is the breaking capacity of C11B4TM025B?

25 kA at 415 V AC (performance level B), which is the maximum fault current it can safely interrupt at that voltage.

What standards does C11B4TM025B comply with?

It complies with EN/IEC 60947-2 for circuit breakers and IEC 60664-1 for pollution degree 3.

Where can I buy C11B4TM025B?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN