The breaker is designed for backplate mounting, accepts front-connect compression lugs or busbars, and fits a 12-module 9 mm pitch footprint — 108 mm wide, 137 mm high, 80 mm deep. The grey (RAL 7016) housing carries IP40 front-face protection and IK07 impact resistance.
For a distribution board fed by a transformer with lower available fault current, this breaker coordinates cleanly with upstream devices rated at the same or higher kA. No earth-leakage protection is built in — if ground-fault detection is needed, add a separate Vigi module or an external RCD.
Where it goes in a panel
The 108 mm width occupies 12 module pitches on a standard 9 mm DIN-rail grid, though the breaker itself does not snap onto DIN rail — it bolts to the backplate. Connection pitch is 35 mm with spreaders, 27 mm without. Neutral is on the left, and the toggle handle gives local on/off control with a green flag indicating auxiliary contact presence.