C11B4TM040B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11B4TM040B — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11B4TM040B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11B4TM040B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11B4TM040B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11B4TM040B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11B4TM040B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11B4TM040B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C11B4TM040B is a ComPacT NSXm 4-pole moulded-case circuit breaker rated 40 A at 40 °C with a 25 kA breaking capacity at 415 V AC — the B performance level for distribution duty. The thermal-magnetic TM-D trip unit gives fixed thermal and magnetic protection, no field-adjustable dials, so what you spec is what protects the feeder.

The 4-pole version switches the neutral as well as the three phases, which is required for TN-S or IT systems where the neutral must be isolated during a fault.

Mounts on a backplate in horizontal or vertical orientation, flat on the back. The 108 mm width fits a 12-module 9 mm pitch DIN cutout. Front connection terminals accept compression lugs or busbars, with a 35 mm connection pitch using spreaders (27 mm without). Neutral is on the left.

Listed as current production — no phase-out notice on record.

Frequently asked questions

What is the breaking capacity of C11B4TM040B?

25 kA at 415 V AC (B performance level) per IEC 60947-2.

What trip unit does this breaker use?

A fixed thermal-magnetic TM-D trip unit rated 40 A at 40 °C.

MPN