The breaker is listed as current production (lifecycle stage: current).
Mounts on a backplate (not DIN rail) — the 9-module pitch (81 mm wide, 137 mm high, 80 mm deep) fits standard panel cutouts. Connection is front-facing via Everlink lugs: accepts 2.5…95 mm² rigid or stranded aluminium/copper, or 2.5…70 mm² flexible copper. The breaker can be mounted horizontally or vertically, flat on the back. IP40 front face (IK07 impact) suits enclosed distribution boards; not rated for washdown.
Rated for 20,000 mechanical cycles and 20,000 electrical cycles at 440 V In/2 (half rated current), or 10,000 at full rated current. The breaker is category A (no intentional short-time delay), so it trips instantaneously on short-circuit.