The Schneider Electric C11F3TM050B is a ComPacT NSXm 3-pole moulded-case circuit breaker rated 50 A at 40 °C with a TM-D thermal-magnetic trip unit. It carries a 36 kA interrupting capacity at 415 V AC (performance level F), which means it can safely clear a bolted fault up to that level without upstream cascading — sized for distribution panels where the available fault current sits in the 36 kA range. The TM-D trip combines a thermal bimetal for overload protection and a magnetic coil for short-circuit response; no earth-leakage module is integrated.
The 81 mm width occupies 9 module pitches on a standard DIN-rail profile. IP40 front face and IK07 impact resistance handle typical enclosure environments — not washdown-rated, but fine for indoor distribution boards where dust and tool drops are the main concern.