Skip to main content
Schneider Electric C11F3TM040B — Miniature Circuit Breakers (MCB)

Schneider C11F3TM040B ComPacT NSXm MCCB, 40A, 36kA 415V

MPNC11F3TM040B
Active

Schneider Electric ComPacT NSXm, 3-pole MCCB, 40 A thermal-magnetic (TM-D) trip unit, 36 kA interrupting at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11F3TM040B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11F3TM040B — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11F3TM040B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11F3TM040B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches9 module
C11F3TM040B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11F3TM040B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11F3TM040B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
C11F3TM040B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

This breaker mounts to a backplate — no DIN-rail clip, so plan for screw-down or busbar mounting. The 81 mm width and 137 mm height fit standard distribution panel layouts. Connections are front-facing, accepting compression lugs or busbars with a 35 mm pitch (27 mm without spreaders).

Electrical durability is rated at 20,000 cycles at 440 V at rated current, with 10,000 cycles at 440 V at In.

Frequently asked questions

What is C11F3TM040B's interrupting rating?

It carries a 36 kA interrupting capacity at 415 V AC (performance level F), which means it can handle high fault currents typical in industrial distribution panels.

What standards does C11F3TM040B comply with?

It is certified to EN/IEC 60947-2 and is suitable for isolation as defined by that standard.

Where can I buy C11F3TM040B and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN