Skip to main content
Schneider Electric C11F3TM080B — Miniature Circuit Breakers (MCB)

Schneider Electric C11F3TM080B ComPacT NSXm 80A 3P MCCB, 36k

MPNC11F3TM080B
Active

Schneider Electric ComPacT NSXm, C11F3TM080B, 80A 3-pole MCCB, TM-D thermal-magnetic trip, 36 kA at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11F3TM080B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11F3TM080B — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11F3TM080B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C11F3TM080B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches9 module
C11F3TM080B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11F3TM080B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11F3TM080B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C11F3TM080B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

For panel environments above 40 °C, derating applies per the thermal curve — the 80 A figure is the baseline, not a ceiling for hot enclosures. Category A utilisation means it is not specifically designed for motor starting duty — it is a distribution breaker, not a motor circuit protector.

This breaker is for distribution panels — switchboards, sub-distribution boards, and load centres — protecting cables and downstream equipment against overload and short-circuit. It mounts on a backplate, with front-facing connections for compression lugs or busbars. The 9-module pitch (9 x 9 mm = 81 mm width) fits standard modular enclosure cutouts. IP40 rated for indoor use; IK07 impact resistance handles incidental contact during panel servicing.

Frequently asked questions

What are the key ratings of the C11F3TM080B?

Rated 80 A continuous at 40 °C, 3-pole, with a 36 kA breaking capacity at 415 V AC. Trip unit is thermal-magnetic TM-D. Complies with EN/IEC 60947-2.

What is the C11F3TM080B used for?

It is a distribution circuit breaker for overload and short-circuit protection in switchboards and sub-distribution panels. Not intended for motor starting duty.

Where can I buy the C11F3TM080B?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quotation.

MPN