Skip to main content
Schneider Electric C11F6TM032B — Miniature Circuit Breakers (MCB)

Schneider Electric C11F6TM032B ComPacT NSXm MCCB, 32 A, 36 k

MPNC11F6TM032B
Active

Schneider Electric ComPacT NSXm, C11F6TM032B, 4P MCCB, 32 A TM-D trip, 36 kA at 415 V AC, IP40, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11F6TM032B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11F6TM032B — Ratings
ParameterValue
Rated current (In)32 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11F6TM032B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11F6TM032B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11F6TM032B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11F6TM032B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11F6TM032B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
C11F6TM032B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Rated for category A utilisation (no intentional short-time delay), it is built for distribution duty — feeding a sub-panel, a lighting circuit, or a motor control centre feeder.

Mounts on a backplate (not a DIN rail) — the 108 mm wide, 137 mm high, 80 mm deep body takes up 12 module pitches at 9 mm. Connection is front-to-front via compression lugs or busbars, with a 35 mm pitch when using spreaders (27 mm without). That pitch matters when you are laying out a multi-breaker row on a busbar system; plan your spreader kit before the build. IP40 front face and IK07 impact resistance mean it is fine inside a clean indoor enclosure — no special gasketing needed. The toggle handle and flag indicator (green for auxiliary-contact presence) give a quick visual check without opening the door.

Frequently asked questions

What standards does the C11F6TM032B comply with?

It is designed and tested to EN/IEC 60947-2, the standard for low-voltage moulded-case circuit breakers. It also carries suitability for isolation per that same standard.

What is the interrupting rating of the C11F6TM032B?

Performance level F: 36 kA at 415 V AC. That is the maximum fault current it can safely interrupt at that voltage.

Where can I buy the C11F6TM032B?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C11F6TM032B