Skip to main content
Schneider Electric C11H3TM025B — Miniature Circuit Breakers (MCB)

C11H3TM025B ComPacT NSXm 25A 3P 70kA Circuit Breaker, TM-D

MPNC11H3TM025B
Active

Schneider Electric ComPacT NSXm, circuit breaker, 3P, 25 A at 40 °C, TM-D trip unit, 70 kA at 415 V AC, EN/IEC 60947-2, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H3TM025B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H3TM025B — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H3TM025B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11H3TM025B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches9 module
C11H3TM025B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H3TM025B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H3TM025B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11H3TM025B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

What this breaker brings to the panel

The C11H3TM025B is a ComPacT NSXm 63H frame 3-pole circuit breaker rated 25 A at 40 °C with a TM-D thermal-magnetic trip unit.

If your panel runs hotter, you'll need to derate per the thermal curve — the TM-D bimetallic strip responds to both load current and ambient heat. The 3-pole version covers three-phase loads — pumps, conveyors, lighting circuits — and the toggle control gives a clear on/off indication.

The 81 mm width and 137 mm height fit standard DIN-rail enclosures, though it's not a DIN-rail snap-on; it bolts to the backplate. Connection pitch is 35 mm with spreaders, 27 mm without — that matters when you're laying out busbars or compression lugs. Front connections top and bottom keep wiring accessible. IP40 front face and IK07 impact rating mean it's fine for a locked electrical room but not for washdown zones.

Frequently asked questions

What is the breaking capacity of C11H3TM025B?

70 kA at 415 V AC, H performance level, per EN/IEC 60947-2.

What trip unit does C11H3TM025B use?

TM-D thermal-magnetic trip unit, rated 25 A at 40 °C.

Where can I buy C11H3TM025B?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C11H3TM025B