Skip to main content
Schneider Electric C11H3TM040B — Miniature Circuit Breakers (MCB)

Schneider C11H3TM040B ComPacT NSXm 40A 3P MCCB, 70kA

MPNC11H3TM040B
Active

Schneider Electric ComPacT NSXm, circuit breaker, 40 A, 3P, 70 kA 415 V AC, thermal-magnetic TM-D trip unit, IP40, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H3TM040B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H3TM040B — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H3TM040B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11H3TM040B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches9 module
C11H3TM040B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H3TM040B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H3TM040B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11H3TM040B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The IP40 enclosure and IK07 impact rating suit panel-mount installations where splash protection is not required.

This allows selective coordination in a distribution panel — downstream faults are cleared by this MCCB while upstream breakers remain closed, keeping other circuits live. Category A utilisation means it is not intended for current-limiting applications but for general distribution.

Environmental and electrical ratings

Relative humidity 0–95 %. Power dissipation is 3.8 W per pole.

Frequently asked questions

What is the breaking capacity of C11H3TM040B?

70 kA at 415 V AC (H performance level), certified to IEC 60947-2.

What compliance documentation does Schneider provide for C11H3TM040B?

The breaker is certified to EN/IEC 60947-2. It carries IP40 and IK07 ratings. For RoHS, REACH, and UL documentation, refer to the manufacturer's compliance portal or request via RFQ.

MPN
C11H3TM040B