Skip to main content
Schneider Electric C11H3TM032L — Miniature Circuit Breakers (MCB)

Schneider Electric C11H3TM032L ComPacT NSXm 32A 3P MCCB, 70k

MPNC11H3TM032L
Active

Schneider Electric ComPacT NSXm, circuit breaker, 3P, 32 A, TM-D trip unit, 70 kA at 415 V AC, EN/IEC 60947-2, grey (RAL 7016).

$195.21 – $285.85Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H3TM032L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H3TM032L — Ratings
ParameterValue
Rated current (In)32 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H3TM032L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11H3TM032L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches9 module
C11H3TM032L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H3TM032L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H3TM032L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11H3TM032L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The 9-module pitch (81 mm wide, 137 mm high, 80 mm deep) mounts on a backplate in horizontal or vertical orientation — fits standard DIN-rail enclosures with the supplied spreaders.

Front-connect terminals use Everlink lugs: accepts 2.5…95 mm² rigid or stranded aluminium/copper, or 2.5…70 mm² flexible copper. Connection pitch is 35 mm with spreaders, 27 mm without — plan your busbar or cable-fanout layout accordingly. IP40 front face, IK07 impact resistance. No earth-leakage protection built in — add a Vigi module downstream if ground-fault detection is required. Mechanical durability is 20,000 cycles; electrical durability varies with load: 20,000 cycles at 440 V In/2, 10,000 at 440 V In, 10,000 at 690 V In/2, 5,000 at 690 V In. The green flag on the front signals presence of auxiliary contacts — no need to open the cover to check.

Suitability for isolation is marked Yes per that standard. Operating altitude: 2000 m without derating, 5000 m with derating. Relative humidity range 0…95 %. The manufacturer provides RoHS, REACH, and UL/IEC compliance documentation on request.

Frequently asked questions

What is the breaking capacity of C11H3TM032L?

70 kA at 415 V AC (performance level H), per EN/IEC 60947-2.

What wire sizes does the C11H3TM032L accept?

Everlink lugs accept 2.5…95 mm² rigid or stranded aluminium/copper, and 2.5…70 mm² flexible copper.

MPN