The 9-module pitch (81 mm wide, 137 mm high, 80 mm deep) mounts on a backplate in horizontal or vertical orientation — fits standard DIN-rail enclosures with the supplied spreaders.
Front-connect terminals use Everlink lugs: accepts 2.5…95 mm² rigid or stranded aluminium/copper, or 2.5…70 mm² flexible copper. Connection pitch is 35 mm with spreaders, 27 mm without — plan your busbar or cable-fanout layout accordingly. IP40 front face, IK07 impact resistance. No earth-leakage protection built in — add a Vigi module downstream if ground-fault detection is required. Mechanical durability is 20,000 cycles; electrical durability varies with load: 20,000 cycles at 440 V In/2, 10,000 at 440 V In, 10,000 at 690 V In/2, 5,000 at 690 V In. The green flag on the front signals presence of auxiliary contacts — no need to open the cover to check.
Suitability for isolation is marked Yes per that standard. Operating altitude: 2000 m without derating, 5000 m with derating. Relative humidity range 0…95 %. The manufacturer provides RoHS, REACH, and UL/IEC compliance documentation on request.