The 81 mm width occupies 9 module pitches at 9 mm each. Connection is front-facing on both line and load sides, using Everlink lugs that accept 2.5 to 95 mm² rigid or stranded aluminium/copper, or 2.5 to 70 mm² flexible copper. With IP40 enclosure protection and IK07 impact resistance, it is suited for indoor distribution boards where occasional mechanical knocks (2 J impact) are expected but not washdown environments.
Electrical durability and environmental limits
Rated for 20,000 mechanical cycles and 20,000 electrical cycles at rated current (In) at 440 V; at half-rated current (In/2) it doubles to 20,000 cycles at 440 V. At 690 V the electrical durability drops to 5,000 cycles at In and 10,000 at In/2 — a typical derating for higher arc voltage. The breaker is suitable for isolation (marked with the isolation symbol per IEC 60947-2).