Skip to main content
Schneider Electric C11H4TM063B — Miniature Circuit Breakers (MCB)

Schneider Electric C11H4TM063B ComPacT NSXm MCCB, 63 A, 70 k

MPNC11H4TM063B
Active

Schneider Electric ComPacT NSXm, circuit breaker, 4P, 63 A, TM-D trip unit, 70 kA 415 V AC, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H4TM063B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H4TM063B — Ratings
ParameterValue
Rated current (In)63 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H4TM063B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11H4TM063B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11H4TM063B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H4TM063B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H4TM063B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11H4TM063B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The breaker is designed for backplate mounting, accepts front-connect compression lugs or busbars, and occupies a 12-module 9 mm pitch width (108 mm). The grey RAL 7016 enclosure carries IP40 and IK07 ratings, so it withstands finger-probe ingress and moderate mechanical impact in an enclosed panel.

The connection pitch is 35 mm with spreaders, 27 mm without — verify busbar or lug spacing before panel layout. Neutral sits on the left. Upside and downside connections are both front-accessible, which simplifies wiring in a standard distribution board.

Frequently asked questions

What is the breaking capacity of C11H4TM063B?

Performance level H gives 70 kA at 415 V AC, defined per IEC 60947-2. That means the breaker can safely interrupt a fault current up to 70 kA at that voltage without failing or cascading upstream.

MPN
C11H4TM063B