Skip to main content
Schneider Electric C11H4TM080B — Miniature Circuit Breakers (MCB)

C11H4TM080B ComPacT NSXm 80A 4P MCCB, 70kA 415V AC

MPNC11H4TM080B
Active

Schneider Electric ComPacT NSXm, C11H4TM080B, 80A 4P MCCB, 70kA 415V AC, thermal-magnetic TM-D trip unit, IP40, grey RAL 7016.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H4TM080B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H4TM080B — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H4TM080B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C11H4TM080B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11H4TM080B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H4TM080B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H4TM080B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C11H4TM080B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

What this MCCB is and what it does

The C11H4TM080B is a Schneider Electric ComPacT NSXm moulded-case circuit breaker — 80 A, 4-pole, with a thermal-magnetic TM-D trip unit. That 80 A rating at 40 °C is the continuous current it carries without tripping; the TM-D trip handles overloads (thermal) and short-circuits (magnetic) in one package. The 70 kA breaking capacity at 415 V AC (performance level H) tells you it can safely interrupt a fault current up to that level without welding contacts or venting gas into the panel — that's the SCCR headroom a site electrical engineer needs for coordination studies. It's built to EN/IEC 60947-2, the standard for low-voltage switchgear and controlgear — specifically Category A, meaning it's not intended for selective coordination with downstream breakers under short-circuit conditions. The 4-pole configuration (4P) switches all three phases plus neutral, with the neutral on the left. Suitability for isolation is confirmed per IEC 60947-2, so it can serve as a visible-break disconnect when locked off.

Mounting and integration

Mounts on a backplate — horizontal or vertical, flat on the back. The 108 mm width and 137 mm height take up 12 module pitches of 9 mm each on a DIN-rail-compatible backplate. Connection pitch is 35 mm with spreaders, 27 mm without. Terminals accept compression lugs or busbars; both upside and downside connections are front-facing, which keeps wiring accessible in a panel. IP40 enclosure protection means it's sealed against tools and small objects, but not water — fine for a dry indoor panel, not for washdown areas.

Frequently asked questions

Where can I buy C11H4TM080B and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of C11H4TM080B?

70 kA at 415 V AC (performance level H). That's the maximum fault current it can safely interrupt at that voltage, per IEC 60947-2.

What standards does C11H4TM080B comply with?

It complies with EN/IEC 60947-2 for low-voltage switchgear and controlgear, and IEC 60664-1 for pollution degree 3. Suitability for isolation is confirmed per IEC 60947-2.

What is the trip unit type on C11H4TM080B?

Thermal-magnetic TM-D. The thermal element protects against overloads; the magnetic element trips instantaneously on short-circuit. It's a fixed-trip design — no interchangeable rating plugs.

MPN
C11H4TM080B