Skip to main content
Schneider Electric C12F6TM160L — Miniature Circuit Breakers (MCB)

Schneider Electric C12F6TM160L ComPacT NSXm 160A 4P MCCB, 36

MPNC12F6TM160L
Active

Schneider Electric ComPacT NSXm, C12F6TM160L, 4-pole MCCB, 160A thermal-magnetic TM-D trip unit, 36 kA at 415 V AC, IP40, grey RAL 7016.

$355.32Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C12F6TM160L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C12F6TM160L — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C12F6TM160L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C12F6TM160L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C12F6TM160L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C12F6TM160L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C12F6TM160L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C12F6TM160L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

160 A MCCB for distribution boards

The Schneider Electric C12F6TM160L is a ComPacT NSXm 160 A four-pole moulded-case circuit breaker with a thermal-magnetic TM-D trip unit. Its 36 kA breaking capacity at 415 V AC (performance level F) handles high-fault-current distribution panels and sub-distribution boards. Rated 160 A at 40 °C, it covers main feeder or large branch circuits in commercial and light industrial installations.

What the ratings mean for fit

The 36 kA at 415 V AC (Icu) is the maximum short-circuit current the breaker can safely interrupt without damage — critical for installations near large transformers or with high available fault current. The 160 A continuous rating at 40 °C is the load it carries without tripping; derate for higher ambient temperatures per the thermal curve. The TM-D trip unit provides fixed thermal (overload) and magnetic (short-circuit) protection curves, not adjustable — select for a known load profile where you don't need field tuning. Category A utilisation means it is not intended for motor starting duty requiring frequent switching under load.

Panel integration and wiring

Mounts on a backplate in horizontal or vertical orientation. Front connection top and bottom simplifies busbar and cable routing in distribution boards. Everlink lug terminals accept 2.5 to 95 mm² rigid/stranded copper (70 mm² flexible) — sized for the 160 A feed. At 108 mm wide, 137 mm high, 80 mm deep, it occupies 12 module pitches of 9 mm on a DIN-rail-compatible backplate. IP40 enclosure protection keeps dust out of the panel interior; IK07 impact resistance handles incidental tool contact during installation.

Standards and compliance

Designed and tested to EN/IEC 60947-2, the governing standard for low-voltage moulded-case circuit breakers. Suitability for isolation (IEC 60947-2) means it can serve as a visible-break disconnect when open. Pollution degree 3 per IEC 60664-1 suits it for industrial environments with conductive contamination. Overvoltage category III covers fixed-installation distribution boards. No earth-leakage protection integrated — add a separate RCD or RCBO if ground-fault protection is required.

Frequently asked questions

What is the breaking capacity of the C12F6TM160L?

The C12F6TM160L has a 36 kA breaking capacity at 415 V AC (performance level F).

What terminals does the C12F6TM160L use?

It uses Everlink lug terminals accepting 2.5 to 95 mm² rigid/stranded copper wire (70 mm² flexible).

Where can I buy the C12F6TM160L?

The C12F6TM160L is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing.

MPN
C12F6TM160L