Mounts on a backplate in horizontal or vertical orientation — flat on the back, no DIN-rail adapter needed. Connection is front-to-front via Everlink lugs accepting 2.5…95 mm² rigid or stranded copper. The 12-module 9 mm pitch (108 mm wide, 137 mm high, 80 mm deep) fits standard enclosure cutouts for the NSXm frame.
Integration notes for the panel builder
IP40 enclosure protection and IK07 impact resistance suit it for general-purpose indoor panel installation — not washdown, not outdoor. Operating altitude 2000 m without derating; above that, derate per the manufacturer's curve up to 5000 m. Relative humidity 0…95 % non-condensing. The neutral position is left; local signalling flag (green) indicates presence of auxiliary contacts. No earth-leakage protection built in — specify an external Vigi module if ground-fault protection is required.