Skip to main content
Schneider Electric C160H4WM — Miniature Circuit Breakers (MCB)

Schneider Electric C160H4WM ComPacT NS1600H, 1600A, 4P, 70kA

MPNC160H4WM
Active

Schneider Electric ComPacT NS1600H new generation, basic frame C160H4WM, 1600 A at 50 °C, 4P, withdrawable, manually operated, 70 kA Icu at 415 V AC.

$3,492.22 – $9,498.60Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C160H4WM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C160H4WM — Ratings
ParameterValue
Rated current (In)1600 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C160H4WM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)1000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 2000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 2000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C160H4WM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeWithdrawable
Control typeManually operated
C160H4WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C160H4WM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric C160H4WM is a basic frame — a bare, manually operated, withdrawable 4-pole chassis rated 1600 A at 50 °C, part of the ComPacT NS630b…1600 new generation range. It carries no trip unit, no protection module; the buyer adds a separate control unit (Micrologic or similar) to set the protection curves. This frame is the structural and current-carrying foundation for a distribution breaker in a low-voltage switchboard. Withdrawable mounting means the frame slides out of its cradle for inspection or swap without breaking the main power connections — a standard requirement for main and tie breakers in switchgear where maintenance access and arc-flash mitigation drive the design.

Integration — panel and switchgear fit

The frame mounts on a backplate in a withdrawable cradle. Dimensions: 306 mm wide, 260 mm high, 147 mm deep. The 70 mm connection pitch and left-side neutral position match the standard ComPacT NS1600H footprint — verify cutout and busbar alignment against the switchgear manufacturer's drawing before ordering. IP40 protection and IK07 impact resistance suit indoor switchgear installations. Class II insulation on the front face eliminates the need for a protective earth connection on the operator interface.

Standards and approvals — IEC 60947-2 backbone

Rated insulation voltage 800 V AC, rated impulse withstand 8 kV, and suitability for isolation — the frame provides visible isolation when racked out, meeting the safety requirements for a main disconnect.

Frequently asked questions

What is the breaking capacity of C160H4WM?

The C160H4WM frame is rated 85 kA Icu at 240 V AC, 70 kA at 415 V AC, 65 kA at 440 V, 50 kA at 500/525 V, and 42 kA at 660/690 V AC, all per IEC 60947-2. The service breaking capacity Ics at 415 V is 37 kA.

Does C160H4WM include a trip unit?

No. The C160H4WM is a basic frame without protection. A separate control unit (e.g., Micrologic) must be ordered and installed to set the overload, short-circuit, and ground-fault protection curves.

Where can I buy C160H4WM and how is it quoted?

The C160H4WM is sourced through independent distribution. It is quoted to order against an RFQ; availability and current pricing are confirmed at quote time. Submit an RFQ for a firm commercial offer.

MPN
C160H4WM