Skip to main content
Schneider Electric C160H420FM — Miniature Circuit Breakers (MCB)

Schneider Electric C160H420FM ComPacT NS Circuit Breaker, 16

MPNC160H420FM
Active

Schneider Electric ComPacT NS new generation, C160H420FM, 4P fixed circuit breaker, 1600 A MicroLogic 2.0 electronic trip unit, 85 kA Icu at 240 V AC, EN/IEC 60947-2.

$3,617.44Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C160H420FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C160H420FM — Ratings
ParameterValue
Rated current (In)1600 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C160H420FM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C160H420FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C160H420FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C160H420FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C160H420FM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

ComPacT NS new generation — 1600 A distribution breaker

The Schneider Electric C160H420FM is a ComPacT NS new generation 4-pole fixed circuit breaker with a MicroLogic 2.0 electronic trip unit rated 1600 A at 50 °C. Breaking capacity peaks at 85 kA Icu at 220/240 V AC (50/60 Hz) and holds 70 kA at 380/415 V, 65 kA at 440 V, 50 kA at 500/525 V, and 42 kA at 660/690 V — all per IEC 60947-2. The H code (70 kA at 415 V) tells you this is the high-breaking version for heavy fault duty. The LSI protection curve covers overload (long-time) and instantaneous short-circuit; no earth-leakage module is fitted. Thermal memory holds for 20 minutes, so the breaker remembers prior heating on reclose cycles.

Fixed-mount on a backplate, 327 mm high by 280 mm wide by 147 mm deep, with a 70 mm connection pitch. IP40 enclosure protection and IK07 impact resistance suit panel installation in indoor switchboards. Neutral is on the left. Four red LEDs for fault indication and one yellow for overload give local status without opening the panel door. Electrical durability: 1000 cycles at 690 V In, 2000 cycles at 690 V In/2, 2000 cycles at 440 V In, 5000 cycles at 440 V In/2. Mechanical durability is 10,000 cycles.

Designed to EN/IEC 60947-2, overvoltage category III, utilisation category B. Relative humidity range 0–95 %.

Frequently asked questions

How do I get current pricing and availability for C160H420FM?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; availability and current pricing are confirmed at quote time.

What is C160H420FM's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, which is the H breaking capacity code.

What trip unit does C160H420FM use?

A MicroLogic 2.0 electronic trip unit with L (long-time overload) and I (instantaneous short-circuit) protection. No earth-leakage module.

MPN
C160H420FM