Skip to main content
Schneider Electric C16B3TM100 — Miniature Circuit Breakers (MCB)

Schneider Electric C16B3TM100 ComPacT NSX160B, 100 A, 25 kA

MPNC16B3TM100
Active

Schneider Electric ComPacT NSX, NSX160B frame, circuit breaker, 3P, 100 A, TM-D trip unit, 25 kA Icu at 415 V AC.

$209.29 – $606.64Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16B3TM100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16B3TM100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration3P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16B3TM100 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16B3TM100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16B3TM100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16B3TM100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16B3TM100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C16B3TM100 is a 3-pole ComPacT NSX160B circuit breaker with a 100 A thermal-magnetic TM-D trip unit. Thermal-magnetic protection means overload (L) is handled by a bimetal strip, short-circuit (I) by a solenoid — no electronics to fail, no auxiliary power needed.

Deployment context

Mounts flat on a backplate in horizontal or vertical orientation — typical for panelboard or switchboard distribution sections. Front-facing connections on both line and load sides simplify bus-bar and cable routing. The IK07 impact rating handles incidental tool strikes during panel assembly.

Suitability for isolation is confirmed per that standard, so you can use it as a visible-break disconnect in a panel where local isolation is required. Pollution degree 3 (IEC 60664-1) means it tolerates conductive pollution in industrial environments — no conformal coating needed for typical panel conditions.

Frequently asked questions

What is the breaking capacity of C16B3TM100 at 415 V?

25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 440 V it is 20 kA; at 500 V it is 15 kA.

What does the TM-D trip unit protect against?

L (overload) via a thermal bimetal strip and I (short-circuit) via a magnetic solenoid — no ground-fault protection built in (earth-leakage protection is without).

Where can I buy C16B3TM100?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C16B3TM100