Skip to main content
Schneider Electric C16F3TM160C — Miniature Circuit Breakers (MCB)

Schneider Electric C16F3TM160C ComPacT NSX160F MCCB, 160 A,

MPNC16F3TM160C
Active

Schneider Electric ComPacT NSX160F, 160 A, 3-pole, thermal-magnetic (TM-D) trip unit, breaking capacity code F (36 kA at 415 V AC).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16F3TM160C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16F3TM160C — Ratings
ParameterValue
Rated current (In)160 A at 50 °C
Poles configuration3P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16F3TM160C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16F3TM160C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16F3TM160C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16F3TM160C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16F3TM160C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It is rated for distribution applications per EN/IEC 60947-2, with a breaking capacity of 85 kA Icu at 240 V AC and 36 kA Icu at 415 V AC — the F code.

The TM-D trip unit is thermal-magnetic, not electronic, so no auxiliary power is needed for the trip function, and the magnetic pickup is fixed (not adjustable). Suitability for isolation is confirmed per EN/IEC 60947-2, meaning the breaker can serve as a disconnecting means in the circuit.

Mounts on a backplate in horizontal or vertical orientation. Front connections on both line and load sides. Width 105 mm, height 161 mm, depth 86 mm — fits standard panel cutouts for the NSX160 frame. IP40 front face, IK07 impact resistance.

Frequently asked questions

What is C16F3TM160C's breaking capacity at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, which is the F breaking capacity code.

Where can I buy C16F3TM160C and how is it quoted?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for C16F3TM160C?

The breaker is certified to EN/IEC 60947-2, with suitability for isolation confirmed. IP40 and IK07 ratings are per IEC 60529 and IEC 62262 respectively. Pollution degree 3 per IEC 60664-1.

MPN
C16F3TM160C