It is a 4-pole (4P) device with toggle control, designed for distribution applications in commercial and industrial panels.
The C16F4TM100C carries an F breaking capacity code: 36 kA Icu at 380/415 V AC, 85 kA at 220/240 V, and 8 kA at 660/690 V. For a 415 V distribution board, 36 kA Icu gives solid headroom against typical utility fault levels (usually 25–35 kA). The 100 A TM-D trip provides fixed L (thermal overload) and I (magnetic short-circuit) protection; no earth-leakage module is integrated, so downstream RCDs or a separate Vigi add-on handle ground-fault protection.
IP40 enclosure protection keeps out tools and fingers but not moisture — install in a dry enclosure.
Durability and environmental limits
Rated for 40,000 mechanical cycles and 40,000 electrical cycles at 440 V at half rated current (In/2), dropping to 20,000 cycles at full rated current. Relative humidity range 0–95 % non-condensing. IK07 impact resistance handles low-energy knocks.