Skip to main content
Schneider Electric C16H6TM080C — Miniature Circuit Breakers (MCB)

Schneider Electric C16H6TM080C ComPacT NSX160H MCCB, 80A, 70

MPNC16H6TM080C
Active

Schneider Electric ComPacT NSX160H, 4P MCCB, 80 A TM-D trip unit, 70 kA Icu at 415 V AC, toggle control, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16H6TM080C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16H6TM080C — Ratings
ParameterValue
Rated current (In)80 A at 50 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16H6TM080C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16H6TM080C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16H6TM080C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16H6TM080C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16H6TM080C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It is a 4-pole device (4P) with toggle control, built for distribution applications and certified to EN/IEC 60947-2. At 220/240 V it jumps to 100 kA Icu; at 525 V it still holds 35 kA. That kind of headroom keeps selectivity with upstream feeders and avoids a cascade trip on a hard fault.

Mounting and integration in the panel

The 161 mm height, 140 mm width, and 86 mm depth fit the ComPacT NSX cutout pattern; connection pitch is 35 mm. IP40 front protection handles dry indoor environments; the IK07 impact rating survives a tool drop during commissioning.

In a pulp and paper mill, the 80 A rating covers a moderate motor control centre feeder or a distribution sub-panel. The TM-D trip gives thermal overload (L) and magnetic short-circuit (I) protection; no earth-leakage module here, so ground-fault protection needs an external Vigi add-on if the mill's grounding scheme demands it. Electrical durability of 40,000 cycles at 440 V In/2 and 20,000 at full rated current means this breaker outlasts most contactors in the same cabinet on normal switching duty.

Frequently asked questions

Where can I buy C16H6TM080C and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is the breaking capacity of C16H6TM080C at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 440 V it drops to 65 kA; at 500 V it is 50 kA.

What standards does C16H6TM080C comply with?

Certified to EN/IEC 60947-2 for circuit-breaker performance, IEC 60664-1 for pollution degree 3, and IEC 62262 for IK07 impact resistance. Suitability for isolation is confirmed per EN/IEC 60947-2.

MPN
C16H6TM080C