Skip to main content
Schneider Electric C16H6TM160C — Miniature Circuit Breakers (MCB)

C16H6TM160C ComPacT NSX160H 4P 160A Circuit Breaker, 70kA 41

MPNC16H6TM160C
Active

Schneider Electric ComPacT NSX, NSX160H, 4P, 160 A, TM-D trip unit, 70 kA Icu at 415 V AC, toggle control, backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16H6TM160C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16H6TM160C — Ratings
ParameterValue
Rated current (In)160 A at 50 °C
Poles configuration4P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16H6TM160C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16H6TM160C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16H6TM160C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16H6TM160C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16H6TM160C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C16H6TM160C is a Schneider Electric ComPacT NSX160H four-pole (4P) circuit breaker with a TM-D thermal-magnetic trip unit rated 160 A at 50 °C. At 220/240 V AC it rises to 100 kA Icu; at 690 V AC it drops to 10 kA Icu, so confirm the available fault current at your service voltage before specifying.

Mounting, environment, and panel integration

The 140 mm width and 161 mm height fit a standard NSX cutout; depth is 86 mm. Pollution degree 3 (IEC 60664-1) and overvoltage category III mean it's rated for the industrial environment inside a panel where conductive dust and transient surges are expected. IP40 front face keeps tools and fingers out; IK07 impact resistance handles incidental panel-door knocks.

Durability and application class

Rated for 40,000 mechanical cycles and 40,000 electrical cycles at 440 V at half rated current (In/2). At full rated current (In) at 440 V, electrical durability drops to 20,000 cycles; at 690 V In it is 7,500 cycles. The toggle control gives clear visual indication of contact position, consistent with its suitability for isolation.

Frequently asked questions

How do I get pricing and availability for C16H6TM160C?

Pricing and availability are confirmed at quote time against an RFQ through independent distribution. Submit an RFQ for current lead time and price.

What is the breaking capacity of C16H6TM160C at 415 V?

The C16H6TM160C is rated 70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 220/240 V AC it is 100 kA Icu; at 690 V AC it is 10 kA Icu.

What compliance documentation does this breaker carry?

The C16H6TM160C is certified to EN/IEC 60947-2, suitable for isolation per that standard. Pollution degree 3 and overvoltage category III per IEC 60664-1. IP40 and IK07 per IEC 60529 and IEC 62262.

MPN