Overview
It mounts fixed, uses a toggle control, and complies with EN/IEC 60947-2.

Schneider C25B32D160 Compact Nsx, New Generation — now discontinued. Supplied from remaining channel stock; full specifications, lifecycle and same-series options are below.
| Parameter | Value |
|---|---|
| Product / component type | Circuit breaker |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| [In] rated current | 160 A at 40 °C |
| Breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
| Parameter | Value |
|---|---|
| Poles description | 3P |
| Trip unit name | MicroLogic 2.2 |
| Trip unit technology | Electronic |
| Device short name | NSX250B |
| Standards | EN/IEC 60947-2 |
It mounts fixed, uses a toggle control, and complies with EN/IEC 60947-2.