Schneider Electric C25F32D100 — Miniature Circuit Breakers (MCB)

Schneider Electric C25F32D100 ComPacT NSX250F, 100 A, 85 kA

MPNC25F32D100
Active

Schneider Electric ComPacT NSX, NSX250F frame, 3P, 100 A, MicroLogic 2.2 electronic trip unit, 85 kA Icu at 240 V AC, F breaking capacity.

$392.99Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C25F32D100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25F32D100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration3P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25F32D100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25F32D100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25F32D100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25F32D100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25F32D100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSoI

Product details

The C25F32D100 is a Schneider Electric ComPacT NSX circuit breaker on the NSX250F frame — a 3-pole, 100 A unit with a MicroLogic 2.2 electronic trip unit providing LSI protection (long-time overload, short-time short-circuit with fixed delay, instantaneous short-circuit). It's rated for distribution duty per EN/IEC 60947-2 and carries an F breaking capacity code: 36 kA Icu at 415 V AC, with a peak of 85 kA Icu at 240 V AC.

The 85 kA Icu at 240 V AC is the maximum fault current it can safely interrupt at that voltage; at 415 V it's 36 kA, and at 690 V it drops to 8 kA.

Front connections top and bottom, 35 mm connection pitch. IP40 enclosure protection (no washdown rating), IK07 impact resistance. Overvoltage category III suits it for fixed-installation distribution panels. The 161 x 105 x 86 mm footprint (H x W x D) fits standard enclosure layouts.

Frequently asked questions

What is the breaking capacity of C25F32D100 at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What trip unit does C25F32D100 use?

A MicroLogic 2.2 electronic trip unit with LSI protection (long-time, short-time with fixed delay, instantaneous).

Where can I buy C25F32D100 and how is it quoted?

Sourced to order through independent distribution; submit an RFQ for current pricing and availability.

What compliance documentation is available for C25F32D100?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1, with IP40 and IK07 ratings. Specific RoHS/REACH declarations are available from the manufacturer upon request.

MPN