Motor protection breaker, 220 A, magnetic-only trip
That trip unit is designed for short-circuit protection only — no thermal overload — so it pairs with an external motor starter or overload relay for coordinated motor branch protection.
At 480 V AC it still holds 35 kA Icu (UL 60947-4-1), and at 600 V AC it derates to 15 kA. For a 480 V motor control center with an available fault current of 30 kA, that leaves headroom for full selectivity with downstream 18 kA breakers. The 22 kA Icu at 525 V AC covers 50 Hz industrial networks in regions that run 500 V class.
The 105 mm width and 161 mm height fit standard ComPacT NSX cutouts. IP40 front face, IK07 impact rating.