It carries a TM-DC thermal-magnetic trip unit providing LI protection — L for overload (thermal) and I for short-circuit (magnetic). The breaking capacity is 20 kA Icu at 1500 V DC with 4 poles in series, and 50 kA Icu at 1100 V DC with 4 poles in series, both conforming to EN/IEC 60947-2. It is also certified for isolation per the same standard.
This breaker is designed specifically for DC circuits — the network type is DC, and the rated operational voltage is 1500 V DC. At 1100 V DC the same pole configuration delivers 50 kA Icu.
Fixed backplate mount, accepts horizontal or vertical orientation. IP40 enclosure protection (IK07 impact resistance) suits clean indoor panel environments — not rated for washdown.