Skip to main content
Schneider Electric C25N1TM160 — Miniature Circuit Breakers (MCB)

C25N1TM160 ComPacT NSX Circuit Breaker, 160 A, 90 kA Icu

MPNC25N1TM160
Active

Schneider Electric ComPacT NSX, circuit breaker, 1P, 160 A, TM-D trip unit, 90 kA Icu at 240 V AC, EN/IEC 60947-2.

$2.53Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25N1TM160 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25N1TM160 — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration1P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)277 V AC 50/60 Hz
Rated insulation voltage (Ui)750 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIV
C25N1TM160 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles at 440 V In/2 5000 cycles at 440 V In
Mechanical durability (cycles)10000 cycles
C25N1TM160 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25N1TM160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25N1TM160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25N1TM160 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

The C25N1TM160 is a Schneider Electric ComPacT NSX fixed-mount circuit breaker, 1-pole, with a TM-D thermal-magnetic trip unit rated 160 A at 40 °C. The 90 kA Icu at 240 V AC (and 50 kA at 415 V) tells you it safely interrupts faults up to that level without cascading upstream — essential for a distribution panel where fault current can hit those numbers. The thermal-magnetic trip gives L (overload) and I (short-circuit) protection in one unit, so no separate relay is needed for a standard feeder or branch circuit.

Mounts flat on a backplate (vertical or horizontal), 35 mm wide per pole, 161 mm tall, 86 mm deep.

Frequently asked questions

What is the breaking capacity of C25N1TM160?

Rated 90 kA Icu at 220/240 V AC, 50 kA at 380/415 V and 440 V, 36 kA at 500 V, 35 kA at 525 V, and 10 kA at 660/690 V, all per IEC 60947-2.

Where can I buy C25N1TM160?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
C25N1TM160