It's designed for distribution applications and carries a 50 kA Icu breaking capacity at 415 V AC (N breaking capacity code), with higher ratings at lower voltages — 90 kA at 240 V AC and 36 kA at 500 V AC. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection, with the neutral protection set to 1 x Ir (4D).
At 690 V AC the breaker still interrupts 10 kA, which covers most industrial step-down transformer secondaries. The 20,000 electrical cycles at 440 V at half-rated current and 10,000 cycles at full rated current give a solid service life for a main or feeder breaker.
Environmental and installation constraints
IP40 enclosure protection and IK07 impact resistance suit it for clean indoor panels. Overvoltage category III covers fixed-installation distribution boards. Operating altitude is 0–2000 m without derating; above that, derate per the manufacturer's curve. Relative humidity range is 0–95%.