160 A thermal-magnetic breaker, 50 kA at 415 V — ComPacT NSX250N frame
Its breaking capacity is 50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, with a symmetrical rating of 90 kA Icu at 220/240 V AC and 10 kA Icu at 660/690 V AC. The NSX250N frame carries the N breaking capacity code — the standard 50 kA at 415 V tier for distribution panels where fault levels are moderate but not extreme.
The TM-D trip unit provides thermal protection (overload, L) and magnetic protection (short-circuit, I) with fixed settings — no adjustment dials, which simplifies specification but means the breaker is matched to the load at order time.
The 105 mm width per pole (315 mm total for 3P) fits standard ComPacT NSX cutouts. IP40 front face protection keeps tools and fingers out; IK07 impact resistance handles incidental contact during panel work.