Schneider Electric C25N3TM160C — Miniature Circuit Breakers (MCB)

Schneider C25N3TM160C ComPacT NSX 160A 3P Circuit Breaker, 5

MPNC25N3TM160C
Active

Schneider Electric, ComPacT NSX series, circuit breaker, C25N3TM160C, 3P, 160 A, 50 kA Icu at 415 V AC, thermal-magnetic TM-D trip unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25N3TM160C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25N3TM160C — Ratings
ParameterValue
Rated current (In)160 A at 50 °C
Poles configuration3P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25N3TM160C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25N3TM160C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25N3TM160C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25N3TM160C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25N3TM160C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

160 A thermal-magnetic breaker, 50 kA at 415 V — ComPacT NSX250N frame

Its breaking capacity is 50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, with a symmetrical rating of 90 kA Icu at 220/240 V AC and 10 kA Icu at 660/690 V AC. The NSX250N frame carries the N breaking capacity code — the standard 50 kA at 415 V tier for distribution panels where fault levels are moderate but not extreme.

The TM-D trip unit provides thermal protection (overload, L) and magnetic protection (short-circuit, I) with fixed settings — no adjustment dials, which simplifies specification but means the breaker is matched to the load at order time.

The 105 mm width per pole (315 mm total for 3P) fits standard ComPacT NSX cutouts. IP40 front face protection keeps tools and fingers out; IK07 impact resistance handles incidental contact during panel work.

Frequently asked questions

What is the breaking capacity of C25N3TM160C at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, which is the N breaking capacity code for the NSX250N frame.

Where can I buy C25N3TM160C and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote.

What compliance documentation does Schneider provide for C25N3TM160C?

The breaker is certified to EN/IEC 60947-2 and carries suitability for isolation per that standard. Pollution degree 3 per IEC 60664-1 and IK07/IP40 protection ratings are documented. Specific RoHS, REACH, or UL documentation should be requested at quote time as the evidence does not list those marks.