Four poles (4P), toggle-operated, built for distribution duty in backplate-mounted panels. Breaking capacity hits 50 kA Icu at 415 V AC (50/60 Hz) per IEC 60947-2, with 90 kA at 240 V and 10 kA at 690 V — that N breaking-capacity code covers most commercial and industrial service-entrance and feeder applications. The TM-D unit provides L (thermal overload) and I (magnetic short-circuit) protection; neutral protection is set at 1 x Ir (4D). No earth-leakage module is fitted.
Dimensions 161 x 140 x 86 mm (H x W x D). IP40 enclosure, IK07 impact resistance — suitable for enclosed panel installation, not washdown.
Electrical durability and isolation
Mechanical durability is 20,000 cycles; electrical durability ranges from 20,000 cycles at 440 V In/2 down to 5,000 cycles at 690 V In.