Skip to main content
Schneider Electric C25V3TM125

Schneider Electric C25V3TM125

MPNC25V3TM125
Active

Circuit breaker, ComPacT NSX250HB1, 75kA/690VAC, 3 poles, TMD trip unit 125A

$912.81Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25V3TM125 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Adjustable
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Current125 A at 40 °C

All specifications

C25V3TM125 additional specifications
ParameterValue
Breaking capacity codeHB1 75 kA 690 V AC
[Ics] rated service breaking capacity85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Power dissipation per pole9.45 W
Network frequency50/60 Hz
Poles description3P
Protected poles description3D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth86 mm
Width105 mm
Height161 mm
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Trip unit nameTM-D
Number of slots5 slot(s)
Trip unit rating125 A at 40 °C
Device short nameNSX250HB1
Device applicationDistribution
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time delay adjustment range120...400 s at 1.5 x In 15 s at 6 x Ir
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Ii] instantaneous protection pick-up adjustment range1250 A
MPN