What the 100 kA Icu rating means for your panel
Its breaking capacity is 100 kA Icu at 500 V AC, 525 V AC, and 660/690 V AC 50/60 Hz per IEC 60947-2.
Integration and mounting notes
Connection pitch is 35 mm, and both upside and downside connections are front-accessed — no rear bus bar required. The toggle control is manual. IP40 enclosure protection (IK07 impact) suits it for clean indoor panels; not rated for washdown environments.
Designed to EN/IEC 60947-2 for circuit-breaker performance, with suitability for isolation (yes, per that standard). Utilisation category A (non-selectivity for short-circuit) applies — coordination studies should account for this. Electrical durability is 20,000 cycles at 440 V In/2, 10,000 cycles at 440 V In, 10,000 cycles at 690 V In/2, and 5,000 cycles at 690 V In; mechanical durability is 20,000 cycles. Operating altitude is 0–2000 m without derating, 2000–5000 m with derating. Relative humidity range is 0–95 %.