Skip to main content
Schneider Electric C40R35E400 — Miniature Circuit Breakers (MCB)

Schneider C40R35E400 ComPacT NSX circuit breaker, 400 A, 200 kA

MPNC40R35E400
Obsolete

Schneider C40R35E400 Compact Nsx, New Generation — now discontinued, supplied from remaining surplus and broker stock.

$35.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40R35E400 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C40R35E400 — Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Poles configuration3P
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C40R35E400 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C40R35E400 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C40R35E400 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C40R35E400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C40R35E400 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range160...400 A
Trip unit protection functionsLSI

Product details

Overview

The C40R35E400 is a Schneider ComPacT NSX molded case circuit breaker rated 400 A at 40 °C with a 200 kA breaking capacity (Icu) at 690 V AC, built around the MicroLogic 5.3 E electronic trip unit. It carries L, S, and I protection curves, an integrated energy meter, and an LCD display for demand values, power quality, and event logs.

Compared to the C63H4, the C40R35E400 delivers a 200 kA breaking capacity versus 85 kA, making it the correct choice for high-fault-current installations where the C63H4's 85 kA would not clear a 200 kA prospective fault.

MPN
C40R35E400