Skip to main content
Schneider Electric C40R36E400 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C40R36E400 ComPacT NSX 400A, 200kA MCCB

MPNC40R36E400
Active

Schneider Electric, ComPacT NSX series, NSX400R, C40R36E400, 400 A MCCB with MicroLogic 6.3 E electronic trip unit, 200 kA breaking capacity at 415 V AC, 3-pole.

$35.33Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40R36E400 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C40R36E400 — Electrical Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (operating cycles)15000 cycles
C40R36E400 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX400R
C40R36E400 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C40R36E400 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C40R36E400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C40R36E400 is a Schneider Electric ComPacT NSX400R moulded-case circuit breaker (MCCB) from the ComPacT NSX family, rated 400 A at 40 °C with a MicroLogic 6.3 E electronic trip unit. It's a 3-pole, 50/60 Hz device built to EN/IEC 60947-2, which governs low-voltage switchgear and controlgear — the standard that defines breaking capacity, utilisation category, and coordination requirements for industrial distribution. At 690 V AC it holds 45 kA Icu. The MicroLogic 6.3 E trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection curves — all adjustable. The electronic trip gives you thermal memory that remembers the last 20 minutes of heating before and after a trip, so reclose-and-trip cycles don't let the cable overheat. It also includes an energy meter and communicates maintenance indicators, demand values, power quality data, and time-stamped event logs. Mechanical durability is 15,000 cycles; electrical durability runs 12,000 cycles at 440 V at half rated current, 6,000 at full rated current — enough for a main breaker in a distribution panel that sees infrequent switching. IP40 and IK07 give it basic indoor panel protection against solid objects and 2 J impact.

The 140 mm width, 255 mm height, and 110 mm depth fit a standard MCCB cutout in a backplate-mounted panel. Toggle control with an LCD display on the trip unit gives local status and settings visibility without opening the door.

Frequently asked questions

What are the key protection settings on the MicroLogic 6.3 E trip unit?

The MicroLogic 6.3 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection, all adjustable. It includes 20-minute thermal memory and energy metering.

What breaking capacity does C40R36E400 have at 415 V?

200 kA Icu at 380/415 V AC, 50/60 Hz per IEC 60947-2. At 690 V it's 45 kA Icu.

MPN
C40R36E400