Schneider Electric C40V45E400 — Miniature Circuit Breakers (MCB)

Schneider Electric C40V45E400 ComPacT NSX400HB1, 400 A, 85 k

MPNC40V45E400
Active

Schneider Electric ComPacT NSX, NSX400HB1, 4P, 400 A at 40 °C, 85 kA Icu at 500 V AC, MicroLogic 5.3 E electronic trip unit, LCD display, toggle control.

$23.72Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40V45E400 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C40V45E400 — Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C40V45E400 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C40V45E400 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C40V45E400 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C40V45E400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C40V45E400 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range160...400 A
Trip unit protection functionsLSI

Product details

The Schneider Electric C40V45E400 is a ComPacT NSX400HB1 molded-case circuit breaker rated 400 A at 40 °C, with an 85 kA Icu breaking capacity at 500 V AC (50/60 Hz) per IEC 60947-2. It carries an electronic MicroLogic 5.3 E trip unit with L, S, and I protection curves, plus an LCD display for energy metering and event logging.

The 400 A trip rating at 40 °C sets the continuous current limit in a 40 °C ambient. That's a high-fault rating for a 400 A frame, suitable for transformer secondaries or industrial mains. The MicroLogic 5.3 E trip unit is fully electronic, offering long-time (L), short-time (S), and instantaneous (I) protection. It also logs energy metering data, demand current, power quality indicators, and time-stamped events — useful for a facility engineer tracking load profiles or coordinating with upstream breakers. Mechanical durability is rated at 15,000 cycles, and electrical durability at 12,000 cycles at 440 V at half rated current (In/2), or 6,000 cycles at full In. That's a solid lifespan for a distribution breaker — it'll handle years of routine switching in a panel without wearing out the contacts.

This is a 4-pole breaker, 185 mm wide, 255 mm tall, 110 mm deep, with a 45 mm pole pitch. It mounts flat on a backplate — no DIN rail here; it bolts directly to the panel's mounting surface. Front connections both top and bottom make wiring straightforward in a dead-front enclosure. The toggle handle and LCD display are up front, and the six accessory slots let you add shunt trips, auxiliary contacts, or communication modules without pulling the breaker.

Frequently asked questions

How do I get current pricing and availability for C40V45E400?

Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the storefront for a current quote.

What is the closest pin-compatible alternative to C40V45E400 in this component family?

There is no direct pin-compatible alternative listed; this order code is the specific NSX400HB1 variant with the MicroLogic 5.3 E trip unit. Other trip unit options (e.g., MicroLogic 2.3 or 6.3) exist in the ComPacT NSX family but require different order codes and may change protection curves or metering capability.

What compliance documentation does this brand provide for C40V45E400?

The breaker is certified to EN/IEC 60947-2, with pollution degree 3 per IEC 60664-1 and overvoltage category III. It carries an IK07 impact rating. Standard compliance documentation (declaration of conformity, test reports) is available from the manufacturer upon request.

MPN