Skip to main content
Schneider Electric C40V46E400 — Residual Current Breakers (RCCB/RCBO)

Schneider C40V46E400 ComPacT NSX MCCB, 400 A, 85 kA, 4-pole

MPNC40V46E400
Obsolete

Schneider C40V46E400 Compact Nsx, New Generation — now discontinued. Supplied from remaining channel stock; full specifications, lifecycle and same-series options are below.

$2,064.75 – $2,146.19Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40V46E400 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C40V46E400 — Electrical Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (operating cycles)15000 cycles
C40V46E400 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX400HB1
C40V46E400 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C40V46E400 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C40V46E400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Overview

The C40V46E400 is a Schneider ComPacT NSX molded case circuit breaker with a 400 A MicroLogic 6.3 E electronic trip unit, rated 690 V AC and 85 kA IC. It is a 4-pole fixed-mount unit with an LCD display and toggle control, designed for distribution applications. The part remains in active production.

The C40V46E400 is an active production part with no end-of-life notice. For lead time and pricing, submit an RFQ.

MPN
C40V46E400