Skip to main content
Schneider Electric CR1F1504G7 — Contactors

CR1F1504G7 TeSys F Magnetic Latching Contactor, 150 A, 4-Pol

MPNCR1F1504G7
Obsolete

Schneider Electric TeSys F CR1F1504G7, magnetic latching contactor, 4-pole, 150 A rated operational current (AC-4), 250 A (AC-1), 127 V AC/DC control circuit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

CR1F1504G7 — Identification
ParameterValue
Product / component typeMagnetic latching contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
CR1F1504G7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)1000 V AC 25...200 Hz
Utilisation categoryAC-1 AC-4 AC-3
CR1F1504G7 — Contacts & Poles
ParameterValue
Pole configuration4P
CR1F1504G7 — Environmental
ParameterValue
IP degree of protectionIP20 front face IEC 60529
Operating altitude9842.52 ft (3000 m) without derating
Protective treatment / pollution degreeTH
CR1F1504G7 — Approvals
ParameterValue
StandardsBS 5424 VDE 0660 IEC 60947-4 JEM 1038 NF C 63-110
CR1F1504G7 — Mechanical
ParameterValue
Width7.9 in (201.5 mm)
Height6.7 in (170 mm)
Depth6.7 in (171 mm)

Product details

Part Identification and Function

The CR1F1504G7 is a TeSys F magnetic latching contactor from Schneider Electric, configured as a 4-pole device with 4 normally open power poles. It is designed for motor control and resistive load switching, rated for utilisation categories AC-1, AC-3, and AC-4. Rated operational current is 150 A under AC-4 duty at ≤ 440 V (40 °C), with a higher 250 A rating under AC-1 for resistive loads. This means the contactor is sized for heavy-duty motor starting and reversing applications where AC-4 ratings govern the switching of inrush currents.

Motor power capability spans 40 kW at 220–230 V AC up to 100 kW at 690 V AC (50/60 Hz). Under UL/CSA ratings, it handles 125 hp at 575–600 V for three-phase motors. These figures define the maximum motor frame size this contactor can switch across common global voltage standards. Rated breaking capacity is 1500 A at 220–440 V for the power circuit, reducing to 450 A at 1000 V. This ensures the contactor can interrupt fault currents within its rated voltage range without welding or excessive arcing — critical for coordination with upstream protective devices. The control circuit operates on 127 V AC (50–400 Hz) or 127 V DC, with latching and unlatching voltage limits of 0.85–1.1 Uc. Average consumption is 1260 VA during latching and 10 VA during unlatching — the high inrush for the latching pulse must be factored into control transformer sizing. This suits applications with moderate cycling demands — not continuous high-speed pick-and-drop operations.

The CR1F1504G7 is certified to IEC 60947-4, BS 5424, VDE 0660, JEM 1038, and NF C 63-110. Rated insulation voltage is 1000 V per IEC 60947-4 and IEC 60158-1, with a VDE 0110 group C rating of 1500 V. These certifications confirm the contactor meets international standards for low-voltage switchgear and motor control. The TH protective treatment indicates suitability for tropical environments with humidity and condensation.

Dimensions are 6.7 in (171 mm) depth, 7.9 in (201.5 mm) width, and 6.7 in (170 mm) height — a compact footprint for a 150 A rated contactor, but panel layout must account for the 201.5 mm width across four pole connections. Power circuit connections accept lugs, ring terminals, bars (up to 2 x 25 x 3 mm), or connectors up to 120 mm². Tightening torque is 159.3 lbf·in (18 N·m) — a calibrated torque wrench is required for termination to avoid high-resistance joints. Associated fuse rating is 160 A aM or gG at ≤ 440 V for the power circuit, or 250 A BS88. This guides the selection of upstream short-circuit protection for type 2 coordination.

As a magnetic latching contactor, it maintains its switched state without continuous coil power — relevant for applications where coil power savings or hold-in current reduction is required. This is a distinct subset within the TeSys F family; verify that the latching function is required for your control scheme before specifying.

Frequently asked questions

What are the key ratings for the CR1F1504G7?

Rated operational current is 150 A AC-4 / 250 A AC-1 at ≤ 440 V. Motor power ranges from 40 kW at 230 V to 100 kW at 690 V AC. Control voltage is 127 V AC/DC. Breaking capacity is 1500 A at 440 V. It is a 4-pole magnetic latching contactor with 4 NO power poles.

What standards does the CR1F1504G7 comply with?

It is certified to IEC 60947-4, BS 5424, VDE 0660, JEM 1038, and NF C 63-110. Rated insulation voltage is 1000 V per IEC 60947-4 and IEC 60158-1. Front-face protection is IP20.

What is the mounting method for the CR1F1504G7?

It mounts on a notched AM1-EC DIN rail or directly to a panel. Dimensions are 6.7 in (171 mm) depth, 7.9 in (201.5 mm) width, and 6.7 in (170 mm) height.

What is the closest alternative to the CR1F1504G7 in the TeSys F family?

Within the TeSys F range, the closest alternative would be a non-latching (electrically held) contactor of similar current rating, such as the LC1F series. The CR1F series is specifically the magnetic latching variant; switching to an LC1F requires a control circuit redesign to provide continuous coil power. No direct pin-compatible drop-in exists between latching and non-latching variants due to the different coil drive requirements.

MPN