Schneider Electric TeSys F magnetic latching contactor, CR1F150FZ7, 3P (3 NO), 150 A rated operational current, 110 V DC coil, 75 kW motor power at 400 V AC-4.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

CR1F150FZ7 — Identification
ParameterValue
Product / component typeMagnetic latching contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
CR1F150FZ7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)1000 V AC 25...200 Hz
Utilisation categoryAC-1 AC-4 AC-3
CR1F150FZ7 — Contacts & Poles
ParameterValue
Pole configuration3P
CR1F150FZ7 — Environmental
ParameterValue
Operating altitude9842.52 ft (3000 m) without derating
Protective treatment / pollution degreeTC
CR1F150FZ7 — Mechanical
ParameterValue
Width6.4 in (163.5 mm)
Height6.7 in (170 mm)
Depth6.7 in (171 mm)

Product details

The CR1F150FZ7 is a TeSys F magnetic latching contactor from Schneider Electric, configured with 3 normally open power poles and rated for 150 A operational current in AC-3 duty at 40 °C.

Control Circuit and Latching Behaviour

The 110 V DC control circuit draws 500 W during the latching pulse and only 15 W during unlatching, so the coil is energised only transiently. The control voltage limits are 0.85 to 1.1 times Uc for both latching and unlatching, meaning the supply must hold within 93.5–121 V DC for reliable operation. Operating time is 35–40 ms to latch and 50–100 ms to unlatch.

Thermal and Electrical Ratings

Rated insulation voltage is 1000 V per IEC 60947-4 and BS 775, with a rated impulse withstand voltage suitable for 1500 V group C per VDE 0110. The rated short-time withstand current holds 1200 A for 10 seconds at 40 °C, and the rated breaking capacity reaches 1500 A at 220–440 V. Average impedance per pole is 0.45 mOhm, so power dissipation runs 6 W per pole in AC-3 and 18 W per pole in AC-1 duty. Associated fuse protection is 160 A aM or 250 A gG at up to 440 V.

Power connections accept lugs, ring terminals, or bars up to 120 mm², bolted at a tightening torque of 18 N·m.

Frequently asked questions

What are the key ratings for the CR1F150FZ7?

Rated operational current is 150 A in AC-3 at 40 °C, with motor power capability of 75 kW at 400 V AC-4. The control circuit is 110 V DC, and the rated insulation voltage is 1000 V per IEC 60947-4.

What is the operating temperature range for this contactor?

The operating ambient temperature range is –15 to 70 °C, with storage from –60 to 80 °C.