Skip to main content
Schneider Electric CR1F185PF7 — Contactors

CR1F185PF7 TeSys F Magnetic Latching Contactor, 185 A, 90 kW

MPNCR1F185PF7
Active

Schneider Electric TeSys F magnetic latching contactor, CR1F185PF7, 3P (3 NO), 185 A rated operational current, 90 kW at 400 V AC-4, 230 V & 110 V AC/DC coil.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

CR1F185PF7 — Identification
ParameterValue
Product / component typeMagnetic latching contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
CR1F185PF7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)1000 V AC 25...200 Hz
Utilisation categoryAC-4 AC-3 AC-1
CR1F185PF7 — Contacts & Poles
ParameterValue
Pole configuration3P
CR1F185PF7 — Environmental
ParameterValue
Operating altitude3000 m without derating
Protective treatment / pollution degreeTC
CR1F185PF7 — Mechanical
ParameterValue
Width168.5 mm
Height174 mm
Depth181 mm

Product details

It is a 3-pole (3 NO) device rated for 185 A operational current and 90 kW at 400 V AC under AC-4 duty — the category for reversing, inching, and plugging applications where the contactor makes and breaks motor starting current repeatedly. The magnetic latching mechanism holds the contacts closed without continuous coil power — the coil draws 1750 VA during the latching pulse and only 11 VA to unlatch, making it suitable for applications where sustained coil power is undesirable or where a power loss must not drop out the load. Control voltage is dual-rated for 230 V and 110 V, both AC (50-400 Hz) and DC, with a latching and unlatching tolerance of 0.85 to 1.1 times Uc.

Sourcing Reality — Obsolete Status

If you are maintaining a panel with this contactor and need a drop-in replacement, verify the mounting footprint, coil voltage, and power ratings against a current TeSys F or TeSys Giga equivalent — the physical dimensions (181 mm depth, 168.5 mm width, 174 mm height) and bolted power connections will guide the mechanical fit check.

For less severe AC-3 duty (starting, stopping at rated load), the operational current is 185 A at <= 440 V, which covers most standard motor starting applications. Rated insulation voltage (Ui) is 1000 V per IEC 60947-4 and BS 775, with a VDE 0110 Group C rating of 1500 V — this gives headroom for 690 V or 1000 V line supplies. The rated short-time withstand current (Icw) is 1500 A for up to 10 seconds at 40 °C, which supports coordination with upstream protective devices. Operating altitude is 3000 m without derating, and the ambient temperature range is -15 to 70 °C — suitable for most indoor industrial environments without forced cooling. Associated fuse recommendations are 200 A aM, 315 A BS88, or 315 A gG at <= 440 V — these are the maximum fuse sizes for short-circuit protection, not the motor overload setting.

Integration Notes

Power circuit connections are bolted — bars (busbar cross-section 25 x 3 mm), lugs-ring terminals up to 150 mm², or connector up to 150 mm². Tightening torque is 18 N.m. The contactor is designed for panel mounting with a 3-pole footprint; no DIN-rail clip is standard for this frame size. Operating time is 35-40 ms for latching and 50-100 ms for unlatching — fast enough for most sequencing but not suitable for high-speed synchronous switching. Maximum operating rate is 120 cycles per hour at 40 °C. Power dissipation per pole is 12 W under AC-3 and 26 W under AC-1 — account for 36-78 W total heat in the enclosure when sizing ventilation.

Frequently asked questions

What replaces the CR1F185PF7?

No official successor order code is listed in the lifecycle record. For a replacement, you will need to cross-reference the mounting dimensions (181 x 168.5 x 174 mm), bolted power connections, 185 A AC-3 rating, and dual 230/110 V AC/DC coil against current TeSys F or TeSys Giga catalog numbers. The physical fit and coil voltage are the critical checks.

What is the motor power rating of the CR1F185PF7?

It is rated for 90 kW at 400 V AC under AC-4 duty (reversing/inching). For AC-3 duty (standard starting), the operational current is 185 A at <= 440 V.

What control voltages does the CR1F185PF7 accept?

The coil accepts 230 V and 110 V, both AC (50-400 Hz) and DC. Latching and unlatching tolerance is 0.85 to 1.1 times the rated control voltage.

What compliance documentation is available for the CR1F185PF7?

The contactor carries insulation voltage ratings per IEC 60947-4, IEC 60158-1, BS 775, and VDE 0110 Group C. For specific RoHS, REACH, or UL documentation, request the manufacturer's compliance declarations through the RFQ process — these are typically available for TeSys F series products but should be confirmed per batch for obsolete parts.

MPN