Skip to main content
Schneider Electric CR1F2654U7 — Contactors

Schneider CR1F2654U7 TeSys F Magnetic Latching Contactor, 26

MPNCR1F2654U7
Active

Schneider Electric TeSys F CR1F2654U7, magnetic latching contactor, 4-pole, 265 A rated operational current, 240 V AC 50/60 Hz coil.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

CR1F2654U7 — Identification
ParameterValue
Product / component typeMagnetic latching contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
CR1F2654U7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)1000 V AC 25...200 Hz
Utilisation categoryAC-1 AC-3 AC-4
CR1F2654U7 — Contacts & Poles
ParameterValue
Pole configuration4P
CR1F2654U7 — Environmental
ParameterValue
IP degree of protectionIP20 front face IEC 60529
Operating altitude9842.52 ft (3000 m) without derating
Protective treatment / pollution degreeTH
CR1F2654U7 — Approvals
ParameterValue
StandardsBS 5424 NF C 63-110 IEC 60947-4 VDE 0660 JEM 1038
CR1F2654U7 — Mechanical
ParameterValue
Width9.6 in (244.5 mm)
Height8.0 in (203 mm)
Depth8.4 in (213 mm)

Product details

The Schneider CR1F2654U7 is a TeSys F magnetic latching contactor — a 4-pole, DC-operated device that holds its state without continuous coil power. Rated for motor control and resistive loads across AC-1, AC-3, and AC-4 utilisation categories, it switches up to 265 A at 440 V AC (AC-3 duty) and handles motor power up to 160 kW at 690 V AC. The latching coil draws 1800 VA on closure and 12 VA holding, meaning the control circuit only needs a pulse to change state, not a sustained signal. The 240 V AC 50/60 Hz control circuit has a latching and unlatching voltage range of 0.85 to 1.1 Uc. Power connections accept lugs, ring terminals, or bars up to 240 mm².

For resistive loads (AC-1), the thermal current Ith is 350 A at 50 Hz, with average impedance of 0.32 mOhm per pole. Power dissipation runs 22 W per pole in AC-3 and 39 W in AC-1, so panel ventilation or spacing matters when grouping multiple contactors. Rated breaking capacity is 2450 A at 440 V for the power circuit, dropping to 800 A at 1000 V. Rated insulation voltage is 1000 V per IEC 60947-4 and BS 775, with a VDE 0110 group C rating of 1500 V. For UL/CSA installations, motor power ratings are 175 hp at 575-600 V AC and 150 hp at 460-480 V AC for three-phase motors. Associated fuse protection calls for 315 A aM or 400 A gG fuses at ≤ 440 V for the power circuit.

The CR1F2654U7 complies with BS 5424, NF C 63-110, IEC 60947-4, VDE 0660, and JEM 1038.

The contactor measures 8.4 in (213 mm) deep, 9.6 in (244.5 mm) wide, and 8.0 in (203 mm) tall. Terminal tightening torque is 309.8 lbf·in (35 N·m). Mounting options include panel mount or notched AM1-EC rail — the rail option simplifies enclosure layout changes without drilling.

Frequently asked questions

What are the key ratings for the CR1F2654U7?

Rated operational current is 265 A in AC-3 duty at ≤ 440 V AC. Motor power reaches 160 kW at 690 V AC. Control circuit voltage is 240 V AC 50/60 Hz. Breaking capacity is 2450 A at 440 V for the power circuit.

What standards does the CR1F2654U7 comply with?

It complies with BS 5424, NF C 63-110, IEC 60947-4, VDE 0660, and JEM 1038. Rated insulation voltage is 1000 V per IEC 60947-4 and BS 775.

What mounting options are available for the CR1F2654U7?

The contactor can be panel mounted or snapped onto a notched AM1-EC rail. It measures 8.4 in deep, 9.6 in wide, and 8.0 in tall.

MPN
CR1F2654U7