Schneider Electric CR1F265T7 — Contactors

Schneider CR1F265T7 TeSys F Magnetic Latching Contactor, 265

MPNCR1F265T7
Active

Schneider Electric TeSys F magnetic latching contactor, 3P (3 NO), 265 A rated operational current AC-3, 480 V AC 50/60 Hz coil, CR1F265T7.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

CR1F265T7 — Identification
ParameterValue
Product / component typeMagnetic latching contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
CR1F265T7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)1000 V AC 25...200 Hz
Utilisation categoryAC-1 AC-4 AC-3
CR1F265T7 — Contacts & Poles
ParameterValue
Pole configuration3P
CR1F265T7 — Environmental
ParameterValue
Operating altitude9842.52 ft (3000 m) without derating
Protective treatment / pollution degreeTC
CR1F265T7 — Mechanical
ParameterValue
Width7.9 in (201.5 mm)
Height8.0 in (203 mm)
Depth8.4 in (213 mm)

Product details

The Schneider CR1F265T7 is a TeSys F magnetic latching contactor with three normally open power poles, rated for 265 A in AC-3 duty at ≤440 V 40 °C. The coil is 480 V AC 50/60 Hz, and it's a latching type: the coil draws 1650 VA to latch, then drops to 9 VA to hold, meaning the coil supply can be removed once latched without the contactor dropping out. That's the core difference from a standard contactor — useful in applications where continuous coil power is undesirable or where you need the contactor to stay closed through a control-voltage dip.

The utilisation categories cover AC-1 (resistive), AC-3 (squirrel-cage motor starting), and AC-4 (plugging/reversing/inching). The 265 A AC-3 rating is the headline motor-switching number; the AC-1 resistive rating is higher at 350 A (Ith 350 A at 50 Hz, 0.32 mOhm average impedance per pole). For AC-4 duty, the rated operational current drops to 245 A at ≤440 V 40 °C — so if your application involves frequent reversing or inching, use the AC-4 figure, not the AC-3 one. The rated breaking capacity is 2450 A at 220–440 V, 2200 A at 500 V, 1700 A at 660/690 V, and 800 A at 1000 V — this is the maximum fault current the contactor can interrupt without damage, not the continuous rating. Associated fuse ratings are 315 A aM, 400 A BS88, and 400 A gG at ≤440 V — these are the maximum fuse sizes for coordinated short-circuit protection.

The control circuit is AC 50/60 Hz at 480 V nominal. The latching coil draws 1650 VA inrush (latching) and 9 VA sealed (unlatching). Operating time is 40 to 75 ms for latching, 50 to 100 ms for unlatching. Control voltage limits are 0.85 to 1.1 Uc for both latching and unlatching — so the coil must see between 408 V and 528 V to reliably operate. The contactor is rated for operation at altitudes up to 3000 m without derating, and ambient temperature range is -15 to 70 °C operating, -60 to 80 °C storage.

Installation and connections

Terminals accept lugs, ring terminals, or bars — up to 240 mm² per pole, or two 32 x 4 mm bars. Tightening torque is 35 N·m (309.8 lbf·in). The contactor is 3-pole (3 NO) with a depth of 213 mm (8.4 in), width 201.5 mm (7.9 in), height 203 mm (8.0 in). Mechanical durability is rated at 1 million cycles. Maximum operating rate is 120 cycles per hour at 40 °C. This is a panel-mount component — typically bolted to a backplate or mounted on a DIN-rail adapter (not included). The protective treatment is TC (standard tropicalised coating).

Frequently asked questions

What are the key ratings I need to check for fit?

The headline rating is 265 A in AC-3 duty at ≤440 V, 40 °C — this is the motor-switching current. For resistive loads (AC-1), the continuous thermal current (Ith) is 350 A at 50 Hz. The coil is 480 V AC 50/60 Hz, latching type. The rated insulation voltage (Ui) is 1000 V per IEC 60947-4. These are the numbers that decide whether this contactor fits your application.

What is the closest alternative in the TeSys F range?

Within the TeSys F magnetic latching contactor family, the closest alternative would differ by coil voltage or current rating. The CR1F265T7 is the 265 A, 480 V AC coil variant. If your control voltage is different (e.g., 110 V or 230 V AC), the corresponding CR1F variant with that coil voltage would be the direct substitute. If you need a different current rating, the TeSys F range covers from around 115 A up to 780 A in the magnetic latching form factor.