Skip to main content
Schneider Electric CR1F4004Q7 — Contactors

Schneider Electric CR1F4004Q7 TeSys F Magnetic Latching Cont

MPNCR1F4004Q7
Obsolete

Schneider Electric TeSys F magnetic latching contactor, CR1F4004Q7, 4 NO, 400 A rated operational current, 380-400 V AC 50/60 Hz control circuit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

CR1F4004Q7 — Identification
ParameterValue
Product / component typeMagnetic latching contactor
Series / rangeTeSys
ApplicationResistive load Motor control
CR1F4004Q7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)1000 V AC 25...200 Hz
Utilisation categoryAC-1 AC-4 AC-3
CR1F4004Q7 — Contacts & Poles
ParameterValue
Pole configuration4P
CR1F4004Q7 — Environmental
ParameterValue
IP degree of protectionIP20 front face IEC 60529
Operating altitude9842.52 ft (3000 m) without derating
Protective treatment / pollution degreeTH
CR1F4004Q7 — Approvals
ParameterValue
StandardsIEC 60947-4 VDE 0660 BS 5424 JEM 1038 NF C 63-110
CR1F4004Q7 — Mechanical
ParameterValue
Width10.3 in (261 mm)
Height8.1 in (206 mm)
Depth8.6 in (219 mm)

Product details

The Schneider Electric CR1F4004Q7 is a TeSys F magnetic latching contactor with 4 normally-open power poles, rated for 400 A operational current in AC-3 duty at up to 440 V AC. It is designed for resistive and motor control applications, switching loads up to 185 kW at 1000 V AC or 250 hp at 460-480 V (UL/CSA). The latching coil holds the main contacts closed without continuous power draw — the control circuit (380-400 V AC, 50/60 Hz) only needs a pulse to latch or unlatch, consuming 1600 VA during the latching pulse and 16 VA during unlatching.

The 400 A AC-3 rating is the motor-switching current — it governs the largest induction motor this contactor can handle under starting and running conditions. For resistive loads (AC-1), the thermal current Ith is 500 A at 50 Hz, with a power dissipation of 70 W per pole.

Mounts on a Notched AM1-EC rail — the standard TeSys F backplate. Dimensions are 8.6 in (219 mm) deep, 10.3 in (261 mm) wide, and 8.1 in (206 mm) tall. Power connections accept lugs or ring terminals for up to 2 x 150 mm² cable, or bars up to 30 x 5 mm. Tightening torque is 35 N.m on the power terminals.

Frequently asked questions

What are the key ratings for CR1F4004Q7?

Rated operational current is 400 A in AC-3 at ≤440 V AC. Control circuit voltage is 380-400 V AC 50/60 Hz. Rated insulation voltage is 1000 V. Breaking capacity is 4000 A at 220-440 V for the power circuit. Motor power is 185 kW at 1000 V AC or 250 hp at 460-480 V (UL/CSA).

What standards does CR1F4004Q7 comply with?

It complies with IEC 60947-4, VDE 0660, BS 5424, JEM 1038, and NF C 63-110. It also carries UL/CSA motor power ratings.

What is the mounting and connection method?

Mounts on a Notched AM1-EC rail. Power connections accept lugs or ring terminals for up to 2 x 150 mm² cable, or bars up to 30 x 5 mm. Tightening torque is 35 N.m.

MPN