Schneider Electric CR1F5004F7
MPNCR1F5004F7
Active
Bistable contactor CR1-F - 4P - AC-1 440V 700 A - coil 110 V
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Product or component type | Magnetic latching contactor |
| Coil voltage | 110 V AC 50...400 Hz 110 V DC standard |
| Voltage | 1000 V IEC 60158-1 1000 V IEC 60947-4 1000 V BS 775 1500 V VDE 0110 group C |
| Control circuit voltage limits | Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc |
| [Ue] rated operational voltage | 1000 V AC 25...200 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Icw] rated short-time withstand current | 4200 A 104 °F (40 °C) - 1 s 4200 A 104 °F (40 °C) - 5 s 4200 A 104 °F (40 °C) - 10 s 3200 A 104 °F (40 °C) - 30 s 2400 A 104 °F (40 °C) - 1 min 1500 A 104 °F (40 °C) - 3 min 1200 A 104 °F (40 °C) - 10 min |
| Breaking capacity | 5000 A at 220...440 V for power circuit 4500 A at 500 V for power circuit 2500 A at 1000 V for power circuit 3560 A at 660/690 V for power circuit |
| [Ie] rated operational current | 500 A (at 700 A (at 460 A (at <104 °F (40 °C)) at <= 440 V AC AC-4 |
| [Ith] conventional free air thermal current | 700 A (at 104 °F (40 °C)) for power circuit |
| Motor power | 335 kW at 1000 V AC 50/60 Hz 335 kW at 690 V AC 50/60 Hz 335 kW at 500...660 V AC 50/60 Hz 295 kW at 440 V AC 50/60 Hz 280 kW at 415 V AC 50/60 Hz 250 kW at 380...400 V AC 50/60 Hz 147 kW at 220...230 V AC 50/60 Hz |
| Motor power HP (UL (CSA)) | 500 hp at 575...600 V AC 50/60 Hz for 3 phase motors 400 hp at 460...480 V AC 50/60 Hz for 3 phase motors 200 hp at 220...240 V AC 50/60 Hz for 3 phase motors 150 hp at 200...208 V AC 50/60 Hz for 3 phase motors |
All specifications
| Parameter | Value |
|---|---|
| Power dissipation per pole | 45 W AC-3 88 W AC-1 |
| Power pole contact composition | 4 NO |
| Poles description | 4P |
| Utilisation category | AC-3 AC-4 AC-1 |
| IP degree of protection | IP20 front face IEC 60529 |
| Mounting support | Notched AM1-EC rail |
| Connections - terminals | lugs-ring terminals 2 0.4 in² (240 mm²) bars 2 40 x 5 mm |
| Operating altitude | 9842.52 ft (3000 m) without derating |
| Depth | 9.1 in (232 mm) |
| Width | 11.3 in (288 mm) |
| Height | 9.4 in (238 mm) |
| Mechanical durability | 1 Mcycles |
| Standards | NF C 63-110 BS 5424 IEC 60947-4 JEM 1038 VDE 0660 |
| Range | TeSys |
| Category | 22336-CTR,F-LINE,AC,OPEN,NONREV |
| Operating time | 40...80 ms latching 50...100 ms unlatching |
| Average impedance | 0.18 mOhm - Ith 700 A 50 Hz |
| Device short name | CR1F |
| Tightening torque | 309.8 lbf.in (35 N.m) |
| Device application | Control |
| Average consumption | 1800 VA AC 50...400 Hz latching 13 VA AC 50...400 Hz unlatching 1800 VA DC latching 13 VA DC unlatching |
| Protective treatment | TH |
| Contactor application | Motor control Resistive load |
| Associated fuse rating | 500 A aM at 800 A BS88 at 800 A gG at <= 440 V for power circuit |
| Maximum operating rate | 120 cyc/h 104 °F (40 °C) |
| Irms rated making capacity | 5000 A for power circuit |
| Ambient air temperature for storage | -76...176 °F (-60...80 °C) |
| Ambient air temperature for operation | 5...158 °F (-15...70 °C) |